Arc Flash Explained: Causes, Dangers and the 4 P Model for Electricians

Arc flash explained for electricians: what causes it, why it kills, and how the 4 P model (Predict, Prevent, Protect, Publish) keeps you safe on site.

Sparky Safety Team
6 min read
Arc Flash Explained: Causes, Dangers and the 4 P Model for Electricians

A Fraction of a Second

Arc flash is one of those hazards that most electricians have heard of but few have seen. That is exactly what makes it so dangerous. A short film from Electrical Safety UK tells the story of an ordinary job going badly wrong, and it is worth walking through because every part of it could happen on a site near you.

Geoff is a facilities manager. He is the duty holder responsible for electrical safety on his site, although he is not an electrical engineer himself. He instructs John, an electrician with 15 years’ experience, to carry out a risk assessment and repair a reported fault on some switchgear. Geoff assumes that by doing this he has discharged his responsibilities.

John makes the equipment dead, opens the panel, tests for dead and starts work. While changing a burnt-out isolator, he drops a spanner. Unknown to John, a contractor who last worked on the switchgear forgot to replace a shroud, leaving two live phase conductors exposed. The spanner bridges them.

Three days later, John dies in hospital from his injuries.

What Actually Happens in an Arc Flash

When the spanner makes contact between the two conductors, the resulting short circuit generates enough heat to vaporise the surrounding metal. That vapour expands rapidly, creating an explosive pressure wave. The video describes what follows:

“…sending a conducting plasma fireball with temperatures in excess of 20,000 degrees centigrade, or four times the surface temperature of the Sun, directly into John’s path.”

The consequences of an arc flash include:

  • Severe external burns from the radiated heat and ignited clothing
  • Internal burns from breathing in superheated gases
  • Blast injuries from the pressure wave
  • Molten metal and shrapnel thrown from the equipment

All of this happens in a fraction of a second. There is no time to react, step back or shield your face.

Why Arc Flash Catches People Out

Switchgear looks harmless. There is no noise, no movement and nothing visually obvious to warn you that a lethal amount of energy is sitting behind the panel. The video makes the point well:

“Arc Flash is a low-frequency, high-consequence event. As such, its rare occurrence can foster a complacency that is utterly disproportionate to the very real consequences that follow when it does happen.”

The film also highlights what it calls a dangerous disconnect. Duty holders and managers make assumptions about how equipment is used and how competent the people working on it are. Those assumptions can be very different from the reality on the shop floor.

In John’s case, three things failed:

  1. Prevention — the shroud was never replaced, so live parts were left exposed
  2. Protection — John had nothing to protect him from the blast
  3. Risk assessment — the root cause, because nobody had properly assessed the job

Notice that John did isolate and test for dead. The problem was the adjacent live conductors. This is why a good safe isolation procedure is essential but not the whole story. You must also ask what else in the enclosure is still live.

The video is blunt about accountability: Geoff and his company will be personally and legally responsible for John’s death. The film does not name specific legislation, but several UK laws apply to a scenario like this:

  • Health and Safety at Work etc. Act 1974 (HASAWA) — employers must protect the health, safety and welfare of employees so far as is reasonably practicable
  • Electricity at Work Regulations 1989 — Regulation 14 restricts work on or near live conductors unless it is unreasonable for them to be dead, it is reasonable to work live, and suitable precautions are taken to prevent injury
  • Management of Health and Safety at Work Regulations 1999 — employers must carry out suitable and sufficient risk assessments
  • Personal Protective Equipment at Work Regulations 1992 — where risk cannot be controlled by other means, suitable PPE must be provided

Handing a job to a qualified electrician does not transfer the duty holder’s responsibility. Geoff’s assumption that he had done enough is exactly the trap these regulations are designed to prevent.

The 4 P Model for Arc Flash Hazard Management

The video then rewinds and shows what should have happened, using a four-stage process.

1. Predict

After an initial assessment, the severity of the thermal effect of an arc flash is calculated for each piece of equipment. This is done in line with IEEE 1584, the standard for performing arc flash hazard calculations. The assessment takes into account:

  • Distance from the equipment to the worker
  • Voltage
  • Prospective fault current
  • Disconnection time

Computer modelling of these factors produces a value for incident energy, measured in calories per square centimetre (cal/cm²). This figure drives everything that follows.

2. Prevent

The next step is to stop the incident from happening by designing it out, eliminating it or removing the hazard at source. With arc flash, complete elimination is very difficult. In practice, prevention means:

  • Reducing the incident energy that would be released, for example through faster disconnection times
  • Keeping people at a safe distance from the equipment

3. Protect

The film is clear about where PPE sits:

“The reality is that often arc flash risk cannot be completely eliminated, and so the last line of defence is to protect with PPE.”

The PPE must be suitable for the level of risk calculated in the earlier steps. Ordinary workwear is not enough. For more on choosing the right kit, see our Complete PPE Guide for Electricians.

4. Publish

The final stage completes the cycle:

  • Risk assessments must be recorded
  • Equipment may need field marking and safety signage
  • Safe systems of work, safety rules and procedures should be devised and documented
  • Training must be delivered to anyone affected

The video adds that risk assessments should, wherever possible, be dynamic and task-based. They should be available to the people doing the work, who should be able to continually reassess the risk based on environmental conditions and the state of the equipment.

The Same Job, Done Properly

In the replay, human error still happens. John believes the equipment is dead, follows his training, and the dropped spanner still makes contact. An arc flash still occurs.

This time, though, two things are different:

  • The incident energy is below 8 cal/cm², thanks to remedial work carried out as a result of the risk assessment
  • John is wearing suitable protective clothing, gloves, helmet and visor

The result is that John is shaken but physically unharmed. As the video puts it, the real success is that he will be at his daughter’s eighth birthday party.

The lesson is that good systems do not rely on people never making mistakes. They make sure that when a mistake happens, nobody dies.

Practical Takeaways for Electricians

  • Work dead wherever possible and prove dead at the point of work every time
  • Look for adjacent live parts before you start, and never assume the last person refitted shrouds and barriers
  • Replace every shroud, barrier and cover you remove, because the next person is relying on you
  • Control your tools — use insulated tools and think about where a dropped spanner would land
  • Read the risk assessment and reassess if the equipment is not as described
  • Wear the arc-rated PPE specified for the task, not whatever is in the van
  • Stop and speak up if something does not look right

For a broader refresher on staying safe around electricity, have a look at our 10 Electrical Safety Tips Every Worker Should Know.

How Sparky Safety Can Help

Electrical hazards, safe isolation, risk assessment and PPE all feature in the Electrotechnical section of the ECS HS&E test, and understanding the reasoning behind them makes the questions far easier to answer.

The Sparky Safety app gives you everything you need to revise in one place:

  • 300+ ECS HS&E practice questions across all 11 topics
  • Mock tests that mirror the real exam
  • Study guides and reference guides covering electrical hazards, PPE and legal duties
  • 10 BS 7671 calculators for everyday work on site

Download the app, work through the Electrotechnical topic, and give yourself the best chance of passing first time, and of going home safe every day after that.

Sparky Safety

Revise on the go with Sparky Safety

400+ practice questions, 10 calculators, and quick reference guides — all in your pocket.

Frequently Asked Questions

What is an arc flash?
An arc flash is a violent release of energy caused when current flows through the air between two live conductors, or between a live conductor and earth. The short circuit vaporises surrounding metal, creating an explosive pressure wave and a plasma fireball that can exceed 20,000°C. It happens in a fraction of a second and can cause fatal burns.
What causes an arc flash?
Common causes include dropped tools bridging live conductors, missing shrouds or barriers, working on or near equipment that has not been fully isolated, damaged insulation, contamination inside switchgear, and equipment failure. Human error during maintenance work on switchgear and distribution boards is one of the most frequent triggers.
What is the 4 P model for arc flash?
The 4 P model is an arc flash hazard management process with four stages: Predict (calculate the incident energy of a potential arc flash), Prevent (design out, eliminate or reduce the hazard at source), Protect (provide PPE suitable for the remaining risk) and Publish (record risk assessments, labelling, safe systems of work and training).
Does safe isolation remove the risk of arc flash?
Safe isolation removes the risk from the conductors you have isolated and proved dead, but it does not protect you from adjacent parts that are still live. If other conductors in the same enclosure remain energised and are not shrouded or screened, a dropped tool can still cause an arc flash. Always check for and guard against adjacent live parts before starting work.